1.5 General
The Telcom Climate Watch System (TCS) is a building monitoring and control system used in
conjunction with one (1) Bard Wall-Mount air-conditioners. The system consists of a state of the art
direct digital controller, the TSC22, one (1) Bard Wall-Mount air-conditioners, and a special "V"
control module that is added to the Bard Wall-Mount air-conditioners. This system provides the
following features.
1.5.1 BUILDING POINTS TO BE MONITORED:
Space Temperature
Space Humidity
Outdoor Temperature
Outdoor Humidity
Occupancy Override Switch
Main Power to Building
Fire Alarm Circuit
Fire Trouble Circuit
Door Alarm Circuit
1.5.2 WALLMOUNT POINTS TO BE MONITORED FOR EACH UNIT:
Blower Airflow
Discharge Air Temperature
Valid Compressor Current Sensor
Compressor Lockout Relay
Dirty Filter Sensor
1.5.3 BUILDING POINTS TO BE CONTROLLED:
Power Transfer Relay
Shelter Alarm Circuit
Door Alarm