5.3.6 Enables Menu
The Enables menu set displays the following information about the
controller.
Economizer Operation Enabled / Disabled
Free Cooling DB Changeover Enabled / Disabled
Free Cooling Enthalpy Changeover Enabled / Disabled
Daylight Savings Time Enabled / Disabled
50 HZ Clock Enabled / Disabled
Zone Humidity Sensor Enabled / Disabled
Zone Dehumidification Enabled / Disabled
From this menu you can display the current status of the
above options and, with the proper authorization, change the current
status. The values displayed for each of these points is updated
every ten (10) seconds. This screen will display as follows:
Pressing the <Up> or <Down> key will scroll forward or
backward respectively through the above list. Once the desired item
is shown on line two of the display, pressing enter will display the
current value of the item. This value will be updated every ten (10)
seconds.
Pressing the <Up> or <Down> key will scroll forward or
backward respectively through the above list displaying the list item
on line one and the status on line two.
To change the displayed status, press the <Change> key. If
you do not have authority to change the status the display will read;
A supervisor authority level is required to change any
options in this menu. If you have authority to change the status the
display will read.
Use the <UP> and <Down> keys to move the status up or
down. Once the new status is displayed press the <Enter> key to
accept the new setpoint. The DAK will respond briefly with:
The display will then revert to the list item display and within 10 seconds the new status will be
updated.
ENABLES
F1 = EDIT MODE
ENTER TO EDIT
Enable Econ.
ENABLED
FC DB CHANGEOVER
DISABLED
FC ENTH.CHANGEOVER
ENABLED
DAYLIGHT SAVINGS TIME
ENABLED
50HZ CLOCK
DISABLED
ZONE HUMID. SENSOR
ENABLED
ZONE DEHUMID CONTROL
DISABLED