6.4.2 SET POINT TAB
The Setpoint screen will allow the user to adjust the Occupied Heating and Cooling, Unoccupied
Heating and Cooling, High and Low, Temperature and Humidity Alarm Setpoints. The Lead/Lag
Changeover hours and the Enthalpy or Dry Bulb Changeover Setpoints can be adjusted from this screen.
Dehumidification setpoint is also changed from this screen. The Continuous Blower may be Enabled or
Disabled from this screen. The lead unit can be changed from this screen. Active cooling, heating, and
dehumidification stages can be monitored.
6.4.2.1 Occupied Cooling Setpoint
The Occupied Cooling Setpoint is used to lower the cooling setpoint to a lower temperature if the
structure is occupied. The Occupied Cooling Setpoint will be the active setpoint if the occupancy
override timer has been triggered and if the zone temperature is above the Occupied Cooling Setpoint.
Once the occupied timer is started the Occupied Cooling Setpoint will be active for two (2) Hours and
then will reset to the Unoccupied Cooling Setpoint. Occupancy override can be canceled after 5 minutes
by pressing the occupancy override button again.
Next to the Occupied Cooling Setpoint value is a scroll bar. Clicking on the right arrow will
increase the Occupied Cooling Setpoint by 0.50 degrees Fahrenheit until the maximum allowed setpoint
of 80.0 Degrees is reached. Clicking on the left arrow will decrease the Occupied Cooling Setpoint by
0.50 degrees Fahrenheit until the minimum allowed setpoint of 72.0 Degrees is reached.