G7 ASD Operation Manual 75
Input Terminal 14 Assignment
Program ⇒ Terminal Selection Parameters ⇒ Input Terminal
Assignment ⇒ 14
This parameter selects the functionality of the #14 input terminal.
Note: The #14 input terminal may be used without the ASD-Multicom
option board.
Without the ASD-Multicom option board the #14 terminal
assignment information will be stored in volatile memory. The
terminal assignment information will be lost if the system is
powered down or reset.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable terminal #14 to 1 of the 68 possible
functions that are listed in
Table 8 on pg. 76.
Direct Access Number — F124
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Input Terminal 15 Assignment
Program ⇒ Terminal Selection Parameters ⇒ Input Terminal
Assignment ⇒ 15
This parameter selects the functionality of the #15 input terminal.
Note: The #15 input terminal may be used without the ASD-Multicom
option board.
Without the ASD-Multicom option board the #15 terminal
assignment information will be stored in volatile memory. The
terminal assignment information will be lost if the system is
powered down or reset.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable terminal #15 to 1 of the 68 possible
functions that are listed in
Table 8 on pg. 76.
Direct Access Number — F125
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Input Terminal 16 Assignment
Program ⇒ Terminal Selection Parameters ⇒ Input Terminal
Assignment ⇒ 16
This parameter selects the functionality of the #16 input terminal.
Note: The #16 input terminal may be used without the ASD-Multicom
option board.
Without the ASD-Multicom option board the #16 terminal
assignment information will be stored in volatile memory. The
terminal assignment information will be lost if the system is
powered down or reset.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable terminal #16 to 1 of the 68 possible
functions that are listed in
Table 8 on pg. 76.
Direct Access Number — F126
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
F124 F126