Note: Input and Output power wires require shielding for CE compliance.
Note: (*) Indicates that the item is one of a set of two parallel cables.
Note: (**) Indicates that a 1.5” conduit orifice is required if using the recommended cable
size.
Table 19. 460-volt G7 ASD Cable/Terminal Specifications.
Model
VT130G7U
MCP
Rating
(Amps)
Typical Wire/Cable Size (AWG or kcmil) Lug Size Range
Input/Output Power
AM, FM, and II
Terminals
Control Terminals
Wire-Size/Lug-Capacity for
Input/Output Power
Recommended Maximum
4015B 15 14 10
20
(3-core shield)
18
(2-core shield)
24 to 8
4025B 15 14 10
4035B 15 14 10
4055B 15 14 10
4080B 20 14 10
4110B 30 12 10
4160B 30 10 4
18 to 4
4220B 50 8 4
4270B 75 8 4
4330B 75 6 4
4400B 100 4 4
4500B 100 3 2 16 to 1
4600B 125 2 2
10 to 1/0
4750B 175 1 **2
410KB 200 2/0 2/0 12 to 4/0
412KB 250 *1/0 *4/0
*(6 to 250)
415KB 300 *2/0 *4/0
420KB 400 *4/0 *500
*(1/0 to 500)
425KB 500 *300 *500
430KB 600 *400 *500
435KB 700 *500 *500