G7 ASD Operation Manual 131
Forward Speed Limit Input
Program ⇒ Torque Setting Parameters ⇒ Torque Speed Limiting
This parameter Enables/Disables the Forward Speed Limit Input control
function. When enabled and operating in the Torque Control mode, the
forward speed limit is controlled by the terminal selected here. If Setting is
selected, the value set at
F426 is used as the Forward Speed Limit input.
Settings:
Disabled
VI/II
RR
RX
RX2 (option)
Setting
Direct Access Number — F425
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Ye s
Forward Speed Limit Level
Program ⇒ Torque Setting Parameters ⇒ Torque Control
This parameter provides a value to be used as the Forward Speed Limit setting
if Setting is selected at
F425.
Direct Access Number — F426
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Ye s
Minimum — 0.00
Maximum — Upper Limit (F012)
Units — Hz
Reverse Speed Limit Input
Program ⇒ Torque Setting Parameters ⇒ Torque Control
This parameter Enables/Disables the Reverse Speed Limit Input control
function. When enabled and operating in the Torque Control mode, the reverse
speed limit is controlled by the terminal selected here. If Setting is selected, the
value set at
F428 is used as the Reverse Speed Limit input.
Settings:
Disabled
VI/II
RR
RX
RX2 (option)
Setting
Direct Access Number — F427
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Ye s
Reverse Speed Limit Level
Program ⇒ Torque Setting Parameters ⇒ Torque Control
This parameter provides a value to be used as the Reverse Speed Limit setting
if Setting is selected at
F427.
Direct Access Number — F428
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Ye s
Minimum — 0.00
Maximum — Upper Limit (F012)
Units — Hz
F425 F428