Remedy:
• Address all non-fatal errors preceding this message.
E308: PORT rec <x>, num of devices cannot = 0
Cause:
• The Number of Devices on Port parameter in record <x> of the A164PORT table is equal to
zero.
Effect:
• Communication on this port will be unavailable.
Remedy:
• Review the section on configuring the A164PORT table (Chapter 4:), and verify that the
Number of Devices on Port is correct.
E399: Non-fatal errors exist in configuration
Cause:
• The BECO2200 DCA encountered non-fatal error in its configuration.
Effect:
• The BECO2200 will be unable to communicate to some or all of the devices configured.
Remedy:
• Address all non-fatal error messages preceding this message.
E400: Error <x> opening port <y>
Cause:
• The BECO2200 DCA failed in its attempt to open the communication port <y>. The error
code returned was <x>.
Effect:
• Communication to all devices configured for this port will be unavailable.
Remedy:
• Ensure that no other application is configured to use port <y>.
• Call the Customer Service department and report this error.
E401: Error <x> setting character port
Cause:
• The BECO2200 DCA failed in its attempt to set the communication port characteristics. The
error code returned was <x>.
Effect:
• Communication to all devices configured for this port will be unavailable.
Remedy:
• Call the Customer Service department and report this error.