A SERVICE OF

logo

Alphabetical reference Commands and Queries Reference
DSP remove a user message from the XMP 2600 front panel display.
Syntax DSP
Parameters none
Category System Type: Sequential
DSP display a message on the XMP 2600 front panel display.
Syntax DSP <string>
Parameters the message to be displayed, limited to 21
characters. Extra characters are truncated.
Category System Type: Sequential
ERR? return the last known Error Code of the XMP 2600 main controller.
The error code is cleared.
Syntax ERR?
Parameters none
Category Status Type: Sequential
ERR? return the last know Power Module error code. The error code is
cleared.
Syntax ERR? <ch>
Parameters the number of the channel to be queried.
Category Status Type: Sequential
FOLD program the type of Foldback to be used by the Power Module when
Current Limit is reached.
Syntax FOLD <ch>,<int>
Parameters the number of the Power Module to be programmed.
the type of Foldback - a decimal value in the range 0
to 4, as detailed below:
0 = no Foldback
1 = retry Foldback
2 = linear Foldback
3 = nonlinear Foldback
4 = shutdown Foldback
See the “current limiting schemes” section of the
Basic Programming chapter for details on Foldback
behavior.
Category Settings Type: Overlapped
FOLD? return the current Foldback selection of the Power Module.
Syntax FOLD? <ch>
Parameters the number of the channel to be queried.
Category Settings Type: Sequential
48 XMP 2600 Programming Manual rev. 1.1