7.4. Communication health management
This option unit has communication health management function.
1. Communication time out function (nciRcvHrtBt)
This value manages the communication time out function. This option unit would initialize the drive
command/setpoint variables and try to stop the motor in case of not receiving an update of the
following variables within the specified Receive Heartbeat time (nciRcvHrtBt).
- nviDrvSpeedStpt
- nviDrvSpeedScale
- nviInvOutFreq
In this case, the inverter output behavior can be determined by the parameter
f851. However, next
selections are invalid.
- None (continued operation)
2. Node health transmission function (nciSndHrtBt, nciMinOutTm)
This option unit informs the network manager to its own health. Network variables controlled by this
function are shown in the table below.
LIU007Z LIU006Z
Variables
nciSndHrtBt nciMinOutTm nciSndHrtBt nciMinOutTm
nvoDrvSpeed
vv
nvoDrvCurnt
vv
nvoDrvVolt
vv
nvoDrvPwr
vv
nvoDrvRunHours
vv
nvoStatusWord
vv
nvoDrvFeedback
vv
nvoInvOutFreq
vv
nvoDrvAlarm
vv
nvoAlarmWord
vv
nvoDrvThermal
nvoMotorThermal
nvoTorque
vv
nvoDrvEnergy
vv
nvoDigitalIn1
vv
nvoDigitalIn2
vv
nvoDigitalIn3
nvoDigitalIn4
nvoDigitalIn5
nvoDigitalIn6
nvoDigitalIn7
nvoDigitalIn8
nvoDigitalInput
nvoAnalogIn1
nvoAnalogIn2
vv
nvoAnalogIn3
nvoEmergStatus --- ---
nvoParamResp --- ---
nvoTypeVer --- ---
v: controlled by nciSndHrtBt and nciMinOutTm