G8000 Series with Isolated Output Installation and Operation Manual
Step 4-5 continues the procedure to start the UPS.
STEP 4
Turn on the DC Input Breaker (72B) on the
external battery cabinet.
BATTERIES LED is “ON”.
STEP 5
*Press the “UPS” button for at least 0.5
seconds.This completes UPS startup
procedure
BYPASS LED is “OFF”.
UPS LED is “ON”.
NOTE
*If the AC switch does not function, contact
Toshiba or authorized representatives.
If the bypass power source is out of
specication, this operation will be inhibited.
In order to switch manually, press the “UPS”
button for 5 seconds or more.
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
UPS SUPPLY
AC - Vo 208 V
AC - Io 50%
CONVERTER
INVERTER
UPS
AC OUTPUT
BATTERIES
BYPASS INPUT
DISCHARGE
EQUAL CHARGE
FLOAT CHARGE
BYPASS
AC INPUT
AC
SWITCH
BYPASS
MOVE 72B TO ‘ON’ POSITION
LED Key
- LED Off
- LED On
- LED Flash