31
G8000 Series with Isolated Output Installation and Operation Manual
TABLE 11.1 RECOMMENDED CRIMP TYPE COMPRESSION LUGS
Wire Size Wire
Strand
Class
Recommendation Crimp tool Required
Burndy type Y35 or Y46
Vendor Cat. No. Color Key Die Index
1/0 B
I
B
Burndy
Ilsco
Burndy
YA25
CRA-1/OL
YA25-LB
Pink
Pink
Black
12 / 348
12 / 348
13
2/0 B
I
B
Burndy
Ilsco
Burndy
YA26
CRA-2/OL
YA27-LB
Black
Black
Orange
13
13
14 / 101
3/0 B
I
B
Burndy
Ilsco
Burndy
YA-27
CRB-3/OL
YA28-LB
Orange
Orange
Purple
14 / 101
14 / 101
15
4/0 B
I
B
Burndy
Ilsco
Burndy
YA28
CRB-4/OL
YA29-LB
Purple
Purple
Yellow
15
15
16
300 MCM B
I
B
Burndy
Ilsco
Burndy
YA30
CRA-30OL
YA32-LB
White
White
Red
17 / 298
17 / 298
18 / 324
TABLE 11.2 RECOMMENDED CABLE SIZE AND TIGHTENING TORQUE FOR 100 KVA AND 150 KVA UPS
Block Number Cable Size Tightening Torque
100 KVA 150 KVA
1 AWG 2/0 or larger AWG 4/0 or larger 275 in-lbs. (3.2 kg-m)
2 AWG 2/0 or larger AWG 4/0 or larger 275 in-lbs. (3.2 kg-m)
3 AWG 2/0 or larger AWG 4/0 or larger 275 in-lbs. (3.2 kg-m)
4 AWG 2/0 or larger AWG 4/0 or larger 275 in-lbs. (3.2 kg-m)
5 AWG 2/0 or larger AWG 4/0 or larger 275 in-lbs. (3.2 kg-m)
6 AWG 2/0 or larger AWG 4/0 or larger 275 in-lbs. (3.2 kg-m)
7 Two AWG 2/0 or larger Two AWG 4/0 or larger 275 in-lbs. (3.2 kg-m)
8 Two AWG 2/0 or larger Two AWG 4/0 or larger 275 in-lbs. (3.2 kg-m)
9 Two AWG 2/0 or larger Two AWG 4/0 or larger 275 in-lbs. (3.2 kg-m)
10 Two AWG 2/0 or larger Two AWG 4/0 or larger 275 in-lbs. (3.2 kg-m)
*11 Two AWG 3/0 or larger Two 300 MCM or larger 275 in-lbs. (3.2 kg-m)
*12 Two AWG 3/0 or larger Two 300 MCM or larger 275 in-lbs. (3.2 kg-m)
13 AWG 2/0 or larger AWG 4/0 or larger 275 in-lbs. (3.2 kg-m)
NOTE: MAXIMUM CABLE SIZE IS 350 MCM
*ONE BATTERY STRING (SEE NOTE, PAGE 36, IF USING MULTIPLE BATTERY STRINGS