User’s Manual
63
Appendix
Note 1) The special module can be designated not only by the assigned register, but
also by the mounting position. The mounting position is designated by a
constant data for the operand C as follows.
(Unit number) × 256 + (Slot number)
H
Slot number (hexadecimal)
Unit number (hexadecimal)
For example, if a special module is mounted on Slot-2, Unit-1 (expansion
unit #1) and allocated to XW020 - YW023, the following two WRITE
instructions function the same.
[ D0100 WRITE RW010 → XW020 ]
[ D0100 WRITE RW010 → H0102 ]
Note 2) The WRITE instruction is not executed as error in the following cases. In
these cases, ERF (instruction error flag = S0051) is set to ON.
• When the operand C is other than a valid constant (see Note 1) or XW/YW
register.
• When the designated special module has been disconnected.
• When no answer error occurs with the designated special module.
• When the number of words transferred exceeds 256 words.
• When the source table of transfer is out of the valid range.
• When the destination table of transfer is out of the valid range.
Unit number Hexadecimal
0 H00
1 H01
2 H02
3 H03
Slot number Hexadecimal
0 H00
1 H01
2 H02
3 H03
4 H04
5 H05
6 H06
7 H07
8 H08
9 H09
10 H0A