EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER
57 74-2958—1
DestB
pass - Has possible states: B
pass On,
B
pass Off or Not Assi
ned
not active
.
This input places the controller in an
untimed
b
pass state or turns off the
b
pass mode. This source is second in
priorit
to DestManOcc under the same
arbitration schemes mentioned above.
Override Button -The wall module Override pushbutton
can command status of B
pass,
Continuous Unoccupied and Not
Assi
ned. This source has the lowest
priorit
status in the above mentioned
schemes. The above mention sources
of override must be either Not Assi
ned
or Off before the Override pushbutton
affects the manual override status in the
Network Wins scheme. All actions, in
this case, taken from the Override
pushbutton are locked out.
B
pass status is a controller-timed
event whose duration is set in B
pTime.
Upon expiration of the timer, the status
returns to Not Assi
ned. The status of
this input can be overridden with the
receipt of Not Assi
ned from
DestManOcc. This, in effect, cancels a
timed b
pass or a continuous
unoccupied mode.
The Override pushbutton can be
confi
ured as Normal
all of the above
mentioned states are possible
, B
pass
Onl
B
pass and Not Assi
ned onl
or
None
effectivel
Disablin
the Override
pushbutton
.
TIME CLOCK (Occ_Time_Clock)
OccTimeClock is the state of the di
ital input confi
ured and
wired to a time clock. When the di
ital input is detected to be
Closed
Occupied
, the scheduled occupanc
will be
OC_OCCUPIED. If the detected state of the di
ital input is
Open
Unoccupied
, then the scheduled occupanc
will be
OC_UNOCCUPIED. If the Occ_Time_Clock is not confi
ured,
then either the DestSchedOcc network input received from a
central control or the time clock that is broadcast from a
Sched_Master confi
ured W7750, controls the occupied
mode.
SCHEDULE MASTER (Sched_Master)
Sched_Master is the state of a di
ital input that is confi
ured
and wired to the W7750. If the Sched_Master input is closed
input shorted
, the node is the schedule master and the state
of the locall
connected time clock will be broadcast out over
the L
ON
W
ORKS
Bus to the other W7750 controllers. If the
Sched_Master input is open, then the node is not a schedule
master and the local time clock will not be sent out over the
L
ON
W
ORKS
Bus even if the time clock input is confi
ured.
However, the DestSchedOcc network input received from a
central control has a hi
her priorit
than the local time clock,
and therefore overrides the local time clock. The W7750
controllers automaticall
bind without the need for a
confi
uration tool.
SETPOINT RAMPING
The W7750 Controller incorporates a rampin
feature that
raduall
chan
es the space setpoints between occupanc
modes. This feature is onl
operational if the network variable
inputs DestSchedOcc, TodEventNext, and Time Until Next
Chan
e Of State
TUNCOS
are bein
used to chan
e the
W7750 Occupanc
mode. The applicable Setpoints are
OaTempMinHtRamp, OaTempMaxHtRamp, MinHtRamp and
MaxHtRamp
for HEAT mode operation
, and
OaTempMinClRamp, OaTempMaxClRamp, MinClRamp and
MaxClRamp
for the COOL mode operation
. See Fi
. 46 for a
pictorial representation of how these setpoints interact.
Durin
recover
operation, the setpoint chan
es at a rate in
de
rees per hour dependin
on the outdoor air temperature. If
there is no outdoor air temperature sensor available, then
MinHtRamp is used as the recover
rate.
Fig. 46. Setpoint ramping parameters with ramp rate
calculation.
NOTE: Recover
rampin
applies between scheduled
heatin
or coolin
setpoint chan
es from
UNOCCUPIED to STANDBY, UNOCCUPIED to
OCCUPIED, and STANDBY to OCCUPIED.
Scheduled setpoint chan
es from OCCUPIED to
UNOCCUPIED or OCCUPIED to STANDBY do not
use a ramped setpoint but instead use a step chan
e
in setpoint. Recover
ramps be
in before the next
scheduled occupanc
time and are ramped from the
setpoint for the existin
scheduled occupanc
state
to the setpoint for the next occupanc
state.
RECOVERY RAMPING FOR HEAT PUMP SYSTEMS
When the node is controllin
heat pump e
uipment, durin
the
recover
ramps, the heatin
setpoint is split into a heat pump
setpoint
for compressors
and an auxiliar
heat setpoint
for
auxiliar
heat sta
es
. The heat pump setpoint is a step
chan
e at the recover
time prior to the OCCUPIED time.
Recover
time is computed from the confi
ured heat recover
ramp rate. The recover
time is calculated:
Recover
time =
OCC setpoint - current setpoint
/ramp rate
See Fi
. 47 for the various setpoints.
HEAT RECOVERY
RAMP RATE
(DEGREES/HOUR)
MaxHtRam
MinHtRam
OaTempMinHtRa OaTempMaxHtRam
OUTDOOR AIR
TEMPERATURE
M10109