A SERVICE OF

logo

F58F COMMERCIAL DUCT MOUNTED ELECTRONIC AIR CLEANER
68-0141—4
7
Attach the cabinet securely to the furnace. The unit can be
attached directly, as shown, or a starting collar can first be
fitted in the furnace opening. Either drill holes and fasten
with sheet metal screws or rivets, or use slip joints. See
Fig. 6.
M3678
Fig. 6. Fasten cabinet to furnace.
Install Turning Vanes
Mount turning vanes inside the elbow or angle fitting that is
directly against the air cleaner cabinet.
Fasten Cabinet To Ductwork
Install a transition when the opening in the air cleaner
cabinet and the duct are different sizes. See Fig. 4.
Fasten the other side of the cabinet to the elbow using
sheet metal screws, rivets, or slip joints as appropriate. If
drilling holes, use locking pliers to help hold the unit in
place during drilling. See Fig. 7.
Install Optional W8600F Air Cleaner Monitor
Choose a location for the W8600F when it is part of the
installation. The monitor is designed to mount next to the
thermostat, or in any convenient visible area (such as utility
room) where it can be seen as it monitors the air cleaner
performance. It shares no electrical connections with the
thermostat. To install, see Fig. 8 and refer to the Installations
Instructions, form 69-1200, included with the monitor.
M3677
LOCKING
PLIERS
TURNING
VANES
Fig. 7. Connect ductwork to air cleaner. Note turning
vanes. Locking pliers hold duct to air cleaner cabinet
during installation.
The W8600F Air Cleaner Monitor is an option available for
use with the F58F The series two F58F requires a solid state
power supply that is compatible with the W8600F driver
board. Any series one F58 can be upgraded to use the
W8600F when the power supply is replaced and the driver
board (included in W8600F kit) is installed.
The W8600F function indicator panel has four liquid crystal
display (LCD) arrowheads that point to ON, BATTERY,
SERVICE or FAULT. See Fig. 8. The arrowheads darken to
indicate the existing EAC condition. See Table 1.
ON
BATTERY
SERVICE
FAULT
Air Cleaner Monitor
FUNCTION
INDICATOR
PANEL
LCD
RESET BUTTON
M11965
Fig. 8. W8600F Air Cleaner Monitor features.