Commercial VisionPRO
®
8000, Commercial PRO
®
7000 And MultiPRO
™
Applications
Remote Sensing
CanbeconfiguredusingHoneywell’slineof10Kohmand
20Kohmcommercialsensors,supportingthefollowing
applicationsthatresidentialthermostatsdon’t:
• TemperatureAveragingNetworks
Because commercial thermostats can be configured
toa20Kohmnetwork,temperatureaveragenetworks
ofanywherefrom1to9+sensorscanbedeployed.
Combinationsof10Kohmand20Kohmsensorsare
use to create the averaging network. The most popular
sensorsaretheTR21andTR21-A(averaging)10Ksensor
andtheTR21andTR21-A20Ksensor.
• RoomTemperatureControl
Performed via a sensing network using the following
sensors:
– WallSensors:TR21-A(10K)foraveragingonly,
TR21(20K),C7189U1005(10K)
– FlushMountSensors:C7772A1012(20K)
– ButtonSensors:C7041P(20K)
• DuctReturnTemperatureControl
Performedusingthefollowing20Ksensors:
C7041B/C7041C/C7770A/C7041J
Unit Vent
• CanbeprogrammedtocontrolASHRAECycle1unitvent
applications.
• Unitventoutside-airdampercanbeprogrammedthrough
the Economizer feature. When the unit vent is on and
occupied, the thermostat will enable the economizer
relay to keep the outside air damper at the maximum
percentage opening. Only maximum percentage
opening is available; the thermostat will not modulate
the damper. When the unit vent is unoccupied, the
thermostat will close the damper.
• RangeStopfeaturecanbeconfiguredtoprogramalow
limit setpoint to prevent equipment damage from freezing.
Commercial Codes
• Complywithcommercialbuildingcodesandmeetthemost
rigorousstandard,California’sTitle24.
• Noholdbuttonisavailable,sothethermostatremains
in permanent schedule.
• Overridebuttonallowsthetenanttooverridean
unoccupied mode for up to 4 hours and can be configured
foranexactoverridesetpoint.Dependingonthepartial
lockout level deployed, a user may override to an exact
setpoint or be given a setpoint range to choose from.
• Pre-OccupancyPurgeandEconomizerfunctionsallow
the building owner to meet all HVAC ventilation codes for
commercial buildings.
Lighting Load Reduction (TOD)
• Commercialbuildingsarefrequentlyautomatedtoturnoff
lighting loads. Lighting loads can use even more energy
than HVAC systems in commercial buildings, and 79%
of commercial buildings have off-hours lighting load
reductioncontrol.Byusingthetime-of-dayrelay(TOD)
inconjunctionwithalightingcontrolsystem,userscan
automatetheirlightingloads.(NotavailableonMultiPRO
™
)
SUBBASE
15
TR21
TR21
TR21-A
THE TR21-A IS A 10K OHM SENSOR