1
General
Specification
Table
2
Contact
Capacity
*
C300
per
UL/NEMA
.
Alarm
and
Trip
Outputs
The
alarm
connected
to
either
of
the
A,
B
or
C
group
of
channels
goes
off
when
the
monitored
temperature
on
one
of
the
channels
in
that
group
rises to
90%
of
the
set
trip
temperature,
or
when
an
RTD
contact
is
broken
for
some
reason
.
If
the
temperature
continues
to
rise,
it
may
eventually
exceed
the
preset
trip
level
.
When
that
happens,
the
trip
indicator
for
either
group
A,
B
or
C
will
light
up
on
the
front
of
the
relay
.
Item
Specification
Temperature
display
range
-
20
to
200°C
Frequency
50/60
Hz
AC
100
to
120
V
Supply
voltage
DC
100
to
125
V
Power
consumption
6
W
Ambient
Operation
-
10
to
60°C
temperature
Storage
-
20
to
70°C
Trip
setting
40
to
195°C
range
Outputs
No
.
of
outputs
6
outputs
(1
trip
&
1
alarm
out-
puts
for
each
group)
Sensor
(RTD)
Pt
100
Ni
100
Inputs
Ni
120
Cu
10
No
.
of
points
8
AC
or
DC
Continuous
Breaking
Resistive
250
V
-
5
A
AC
*
Inductive
5
A
250
V
-
2
A
@
pf
=
0
.4
Resistive
30
V
- 5
A
DC
Inductive
5
A
125
V
-0
.0
7A
@
L/R=7ms