Guide Specification – 3-Phase Static Uninterruptible Power Supply
7
3.2.3 Clearances for installation
Ceiling Level : 20” minimum from top of UPS to ceiling
Front : 40” minimum for maintenance
(Local and regional codes may apply)
Bottom : Knockouts for power cable access
Rear : Zero clearance required
Sides : Zero clearance if using bottom cable access
(Standard knockouts for left/right side
cable access )
Base : Channel mounted
4 SYSTEM PARAMETERS
4.1 UPS Requirements:
4.1.1 General Requirements:
Rated Output Capacity : 80/100/160/225 kVA
(72/90/144/202.5 kW)
AC/DC Rectifier Type : AC/DC multi-level IGBT Rectifier
DC/AC Inverter Type :DC/AC multi-level IGBT Inverter
Inverter
External Dimensions (W) (D) (H)*
80 kVA : 27.6”x 32.8”x 78.7 (80.6)”
100 kVA : 27.6”x 32.8”x 78.7 (80.6)”
160 kVA : 35.4”x 32.8”x 78.7 (80.6)”
225 kVA : 35.4”x 32.8”x 78.7 (80.6)”
* Unit height with fan assembly installed
Weight
80 kVA : 855 lbs
100 kVA : 855 lbs
160 kVA : 1160 lbs
225 kVA : 1230 lbs
Power Cable Access : Bottom, Sides, Top Entry with optional
side cabinet
Paint Color : Black (Munsell N1.5)
4.1.2 AC Input:
Configuration : 3-Phase/3-Wire + Ground
Rated Voltage : 480V
Voltage Variation : +15% to –20%
Rated Frequency : 60Hz
Frequency Variation : +/-10%
Input Power Factor : Greater than 0.99 lagging at 25%-115% load