1600XP Series Installation and Operation Manual
BSDV N Battery Shutdown Voltage – Bat-
tery is discharged down to mini-
mum level.
UPS will shut down.
BTSTFL N Battery Test Failed – Battery not
within specications.
Call Toshiba for service.
BYPOV N Bypass Overvoltage – Bypass
voltage exceeds UPS specica-
tions.
Depends on UPS mode.
BYPUV N Bypass Undervoltage – Bypass
voltage less than UPS specica-
tions.
Depends on UPS mode.
CALL Y Service Call Required – Inspection
of the unit is advised.
Have inspection/service performed.
CHRGOV Y Charger Overvoltage – Battery
Charger not within specications.
Call Toshiba for service.
CLMT N Current Limit – UPS not within
specications.
Call Toshiba for service.
DCER Y Display Cable Error – Display
cable is disconnected.
Connect the display cable.
DCANERR N Communication Error between
Display and Main Controllers.
Call Toshiba for service.
FBYPER N Bypass Frequency Error – Input
frequency outside of UPS speci-
cations.
Depends on UPS mode.
FIER N Input Frequency Error – Input fre-
quency outside of 45-65 Hz range.
Depends on UPS mode.
LB N Low Battery – The battery level
has dropped low (about 90% or
less) during operation. Continued
operation in this mode will deplete
battery and cause output shut
down.
Immediately shut down the load equipment in an
orderly fashion and then press the STOP key.
OL110 N Overload – UPS is overloaded
(110% and above) Unit will switch
to bypass operation or shut down
if no action is taken.
Shut down excess equipment to reduce load.
REYEERR N Communication Error between
RemotEye and UPS.
Ensure RemotEye is connected to UPS. Call
Toshiba for service.
RS232ERR N Communication Error at Service
Port.
Call Toshiba for service.
REYEUER N Communication Error at LAN. Call Toshiba for service.
VDCUVBT N DC Bus Undervoltage During Bat-
tery Test.
Call Toshiba for service.
VIOV N Input Overvoltage – Input voltage
exceeds UPS specications.
Depends on UPS mode.
VIUV N Input Undervoltage – Input voltage
less than UPS specications.
Depends on UPS mode.