(b) Accuracy
The value obtained by the END instruction is added to the current value when the
OUT T or OUT
ST instruction is executed.
The current value is not updated while the timer coil is off even if the OUT T or OUT ST instruction is
executed.
Accuracy of the timer response that is from reading input (X) to output the data is up to "2-scan time
+ timer limit setting".
Figure 9.26 Timer accuracy (in the case of 10ms)
X0
TO
HK8
211 121 121
23 23 23
OUT T0 OUT T0 OUT T0
OUT T0
OUT T0
OUT T0
2
ON
OFF
OFF
OFF
ON
ON
OFF
ON
3
2
3 2 3
[Ladder example]
[Current value update timing]
Program
External input
X0 of CPU module
Coil of T0
Contact of T0
10ms counting
Count at execution of
the END instruction
Current value
0+2=2 2+3=5 5+2=7 7+3=10
END
processing
END
processing
END
processing
END
processing
END
processing
END
processing
Accuracy from when the coil of the timer turns on until
when the contact of the timer turns on
- (1 scan time + timer limit setting) to (1 scan time)
Timing when the coil of the timer turns on
Input reading timing