Product Description
MS-9200UDLS PN 52750:E1 01/27/09 15
• Communication Confirmation (Kissoff) LED
• Touchtone/Rotary dialing
• Programmable Make/Break Ratio
• EIA-232 Printer/PC interface (variable baud rate)
• 80-character LCD display (backlit)
• Real-time clock/calendar with daylight savings time control
• History file with 1,000 event capacity
• Advanced fire technology features:
Automatic drift compensation
Maintenance alert
Detector sensitivity test capability (NFPA 72 compliant)
Automatic device type-code verification
Point trouble identification
• Waterflow selection per module point
• Alarm verification selection per detector point
• Walktest, silent or audible
• PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)
• Silence inhibit timer option per NAC
• Autosilence timer option per NAC
• Continuous, March Time, Temporal or California code for main circuit board
NACs with two-stage capability
• Selectable strobe synchronization per NAC
• Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules,
ACS annunciators or ANN-80 Remote annunciator
• Auto-program (learn mode) reduces installation time. Reports two devices set to
the same address
• Password and key-protected nonvolatile memory
• User programmable password
• Fully programmable from local keypad or optional keyboard
• Optional PK-CD (contains PS-Tools utility) for local or remote Upload/
Download of program and data
• Compatible with Fire-Lite’s newer series devices in LiteSpeed and CLIP mode
(refer to SLC Wiring Manual for a list of compatible addressable devices)
• Compatible with legacy Fire-Lite 300 Series devices in CLIP mode only (refer to
the SLC Wiring Manual for a list of compatible addressable devices)
• Optional 4XTMF module (conventional reverse polarity/city box transmitter)
• ANN-BUS for connection to following optional modules (cannot be used if ACS
annunciators are used):
ANN-80 Remote Annunciator
ANN-I/O LED Driver
ANN-S/PG Printer Module
ANN-RLY Form-C Relay Module
ANN-LED Annunciator Module annunciates alarm, trouble and supervisory
ANN-RLED Annunciator Module annunciates alarms only
• Automated activation of the ACC-25/50(ZS/T) Audio-Command-Center
• Legacy ACS/TERM Annunciators (cannot be used if ANN annunciators are
used):
ACS Series-LED Zone Annunciators
LDM Graphic Annunciator Series
LCD-80F Liquid Crystal Display point annunciator
ACM-8RF Relay Module