Legend and Notes for Table 10
LEGEND:
CO --- Convenient outlet
DISC --- Disconnect
FLA --- F ull load amps
IFM --- Indoor fan motor
LRA --- Locked rotor amps
MCA --- Minimum circuit amps
MOCP --- Maximum over c urrent protection
PE --- Power exhaust
UNPWR CO --- Unpowered convenient outlet
NOTES:
1. In compliance with NEC requirements for multimotor and
combination load e quipment (refer to NEC Articles 430 and
440), the overcurrent protective device for the unit s hall be
fuse or HACR breaker. Canadian units may be fuse or circuit
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply
voltage is greater than 2%. Use the following formula to de-
termine the percentage of voltage imbalance.
% VoltageImbalance =100 x
max voltage deviation from average voltage
averagevoltage
Example: Supply voltage is 230-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
(224 +231 +226)
=
681
3
3
= 227
Determine m aximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% VoltageImbalance = 100 x
4
227
=1.76%
This amount of phase imbalance is satisfactory as it is b elow the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
Economizer 2 Position Damper
Unit Without Economizer or
2 Position Damper
C08631
Fig. 65 -- EconoMi$ert IV Wiring
Step 11 Adjust Factory--Installed Options
Smoke Detectors
Smoke detector(s) will be connected at the Central
Terminal Board (CTB), at terminals marked “Smoke
Shutdown”. Remove jumper JMP 3 when ready to
energize unit.
EconoMi$er IV Occupancy Switch
Refer to Fig. 65 for general EconoMi$er IV wiring.
External occupancy control is managed through a
connection on the Central Terminal Board.
If external occupancy control is desired, connect a time
clock or remotely controlled switch (closed for Occupied,
open for Unoccupied sequence) at terminals marked
OCCUPANCY on CTB. Remove or cut jumper JMP 2 to
complete the installation.
50TCQA