PROGRAM MUX
1- MUX EDIT
2- MUX PROGRAM
3- BUS TYPE
4- AUTO PROGRAM
MUX Edit
Shortcut: 0-PROG, 9-PROGRAM MUX, 1- MUX EDIT
To add MUX devices to the system, use the MUX Edit option. Each device must have a unique
address programmed using the address switches.
The following window appears:
DEVICE TYPE ( )
0- NO DEVICE
2- SINGLE INPUT
3- I/O MODULE
4- MUX SMOKE
5- SMOKE W/FRZ
6- DUAL INPUT
7- OCTAL INPUT
DescriptionModel
0- NO DEVICE
2- SINGLE INPUT D7044/M, D7045, FMM-7045, D7052(Class A)
3- I/O MODULE D7053
4- MUX SMOKE D7050, D7050TH, D343
5- SMOKE W/FRZ Not Used
6- DUAL INPUT D7052(Class B)
7- OCTAL INPUT D7042
Press the number that corresponds with the device you are adding or press [0/Prog] if you are
removing a device. When the device type is selected, the following window appears:
POINT NUMBER
(009 - 255) 009
Enter the address of the point being added, and press [#/Enter]. The device type window
appears again allowing additional devices to be added. Eight points are added at once when
the D7042 is added to the control panel.
MUX Program
Shortcut: 0-PROG, 9-PROGRAM MUX, 2-MUX PROGRAM
To add MUX devices to the system simultaneously while programming an address into the
device itself, use the MUX Program option. This programs a specified address into the device,
and also sets the control panel to use the device.
Warning!
Programming issues!
The D7042 is programmed using switches and cannot be added using the MUX Program fea-
ture. Use MUX Edit instead.
All devices must be removed from MUX bus A before programming by removing power from
the system, disconnecting the wires to the field devices, and re-powering the system. Failure
to disconnect devices results in all devices on loop A being programmed to the new address.
All programming is performed on Bus A, including addresses 129 to 255 that can only be
installed on Bus B for operation. Be sure to connect devices with addresses 129 to 255 to
Bus B, not to Bus A.
8.9.1
8.9.2
90 en | Control Panel Programming Fire Alarm Control Panels